KEWANEE® GAS VALVES
OEM Boiler Parts stocks gas valves for Kewanee® burners.
While we do have a few Eclipse valves left in-stock, we have changed over to using Siemens valves in lieu of Eclipse valves. This decision was based on the cost, the availability and the construction of the Eclipse valves. The Siemens valves are more affordable, readily available and are made of aluminum, not steel.
If you are switching from an Eclipse valve to a Siemens valve, you will also need the Siemens CA-M10R-3, Slotted Drive Arm.
GAS BUTTERFLY VALVE
ADJUSTMENT PROCEDURE
1. Use box end or socket wrench to loosen or tighten ball-joint connectors.
2. To adjust low fire (minimum) fuel setting, loosen ball-joint connector
holding drive rod and manually position butterfly disc to desired opening, then re-tighten connector.
3. For initial start-up: Position actuator arm so internal disc is approximately 15° open.