IRON FIREMAN BUTTERFLY GAS VALVES
OEM Boiler Parts stocks tons of Eclipse butterfly gas valves for Iron Fireman burners.
Part Number 7004800100 Contact us for price & availability.
GAS BUTTERFLY VALVE
ADJUSTMENT PROCEDURE
1. Use box end or socket wrench to loosen or tighten ball-joint connectors.
2. To adjust low fire (minimum) fuel setting, loosen ball-joint connector holding drive rod and manually position butterfly disc to desired opening, then re-tighten connector.
3. For initial start-up: Position actuator arm so internal disc is approximately 15° open.